Professional Sports Arena

Electric Consumption Tests by Clean Air Flow, Inc. installed at the SCR Cabinet and Measured at Switchgear
150 hp Motor

Baseline test prior to installation After Install
File C:\My Documents\XXXFullloadbaselinepsm.log* File C:\My Documents\XXXUnitpsm.log*
Test began at 3/28/03 12:07:47 Test began at 3/28/03 12:42:32
Test ended at 3/28/03 12:17:48 Test ended at 3/28/03 12:52:31

Measurement
Before
After
Units
Change
%Change

Voltage, A Phase, Ave:
Voltage, B Phase, Ave:
Voltage, C Phase, Ave:
Current, A Phase, Ave:
Current, B Phase, Ave:
Current, C Phase, Ave:
Current, Neutral, Ave:
True Power, A Phase, Ave:
True Power, B Phase, Ave:
True Power, C Phase, Ave:
Total True Power:
VA Power, A Phase, Ave:
VA Power, B Phase, Ave:
VA Power, C Phase, Ave:
Total VA Power:
Power Factor, A Phase, Ave:
Power Factor, B Phase, Ave:
Power Factor, C Phase, Ave:
Total Power Factor:
Energy, A Phase:
Energy, B Phase:
Energy, C Phase:
Energy, Total Elapsed:
Energy, estimated per month:
Cost, estimated per month:
(at $0.06500/KWH)

467.0
468.5
466.6
123.3
128.0
121.8
0.0
9346.6
24247.0
30816.8
64410.5
33251.3
34413.6
32824.1
100488.9
0.31
0.72
0.94
0.64
1.561
4.045
5.143
10.749
47033.8
$3057.20
459.8
461.2
459.6
81.9
85.0
79.6
0.0
11554.5
11877.4
21237.5
44669.4
22011.9
22787.0
21406.4
66205.2
0.57
0.60
1.00
0.67
1.923
1.977
3.534
7.434
32637.8
$2121.46

volts
volts
volts
amps
amps
amps
amps
Watts
Watts
Watts
Watts
VA
VA
VA
VA


KWH
KWH
KWH
KWH
KWH

 

-7.2
-7.3
-7.0
-41.4
-43.0
-42.2
0.0
2207.9
-12369.6
-9579.3
-19741.1
-11239.4
-11626.6
-11417.7
-34283.7
0.26
-0.12
0.06
0.03
0.362
-2.068
-1.609
-3.315
-14396.0
$-935.74
-1.5 %
-1.6 %
-1.5 %
-33.6 %
-33.6 %
-34.6 %
0.0 %
23.6 %
-51.0 %
-31.1 %
-30.6 %
-33.8 %
-33.8 %
-34.8 %
-34.1 %
83.9 %
-16.7 %
6.4 %
4.7 %
23.2 %
-51.1 %
-31.3 %
-30.8 %
-30.6 %
-30.6 %

Report Prepared By: Summit Technology PS 3000 Power Quality Analyzer for:
Jerry Owens CES,CEI
Vice President of Operations
Clean Air Flow
525 Great Southwest Parkway
Arlington, TX
Phone: 817-530-2200
Email: jowens@cleanairflow.com


Consumption tests on the EPR are measured by the Summit Technology Power Sight 3000, Power Quality Analyzer which is certified for accuracy within 0.05%.

* XXX = Client Name, removed at Client request.